Device Export Strategy
The table below shows the strategy for exporting data points to Building X based on the device type.
Device Type | Building X Data Point Export Strategy |
BACnet devices | |
APOGEE BACnet FLN Device (including DXR) | If a semantic function is assigned to the device (typical case), create one Building X data point per DL2 property. If no function is assigned to the device, create one Building X data point per descendent, using default property as Building X data point value. |
Desigo PX controller | Create one Building X data point per descendent, using default property as Building X data point value. |
APOGEE BACnet primary controller | Create one Building X data point per descendent, using the default property as Building X data point value. |
DXR2 imported in full TRA/DRA mode | Create one Building X data point per descendent, using default property as Building X data point value. |
Desigo PXC Controller (TRA/NGA) | Create one Building X data point per descendent, using default property as Building X data point value. |
Desigo PXC.A (NGAA) Controller | Create one Building X data point per descendent, using default property as Building X data point value. |
non-BACnet devices | |
APOGEE P2 primary controller | Create one Building X data point per descendent, using default property as Building X data point value. FLNs data points are excluded from this device, however, they are included in their own devices, see APOGEE P2 FLN Device strategy below. |
APOGEE P2 FLN Device | If a semantic function is assigned to the device (typical case), create one Building X data point per Function DL2 property. If no function is assigned to the device, create one Building X data point per DL3 per property. |
IoT-tagged device (e.g. SORIS leaf node) | If a semantic function is assigned to the device (typical case), create one Building X data point per Function DL2 property. If no function is assigned to the device, create one Building X data point per DL3 per property. |
IoT-tagged device (e.g. SORIS container node) | Create one Building X data point per descendent, using default property as Building X data point value. |
Siclimat Controller | Create one Building X data point per descendent, using default property as Building X data point value. |
Modbus Controller | Create one Building X data point per descendent, using default property as Building X data point value. |