Device Export Strategy

The table below shows the strategy for exporting data points to Building X based on the device type.

Device Type

Building X Data Point Export Strategy

BACnet devices

APOGEE BACnet FLN Device (including DXR)

If a semantic function is assigned to the device (typical case), create one Building X data point per DL2 property.

If no function is assigned to the device, create one Building X data point per descendent, using default property as Building X data point value.

Desigo PX controller

Create one Building X data point per descendent, using default property as Building X data point value.

APOGEE BACnet primary controller

Create one Building X data point per descendent, using the default property as Building X data point value.

DXR2 imported in full TRA/DRA mode

Create one Building X data point per descendent, using default property as Building X data point value.

Desigo PXC Controller (TRA/NGA)

Create one Building X data point per descendent, using default property as Building X data point value.

Desigo PXC.A (NGAA) Controller

Create one Building X data point per descendent, using default property as Building X data point value.

non-BACnet devices

APOGEE P2 primary controller

Create one Building X data point per descendent, using default property as Building X data point value.

FLNs data points are excluded from this device, however, they are included in their own devices, see APOGEE P2 FLN Device strategy below.

APOGEE P2 FLN Device

If a semantic function is assigned to the device (typical case), create one Building X data point per Function DL2 property.

If no function is assigned to the device, create one Building X data point per DL3 per property.

IoT-tagged device (e.g. SORIS leaf node)

If a semantic function is assigned to the device (typical case), create one Building X data point per Function DL2 property.

If no function is assigned to the device, create one Building X data point per DL3 per property.

IoT-tagged device (e.g. SORIS container node)

Create one Building X data point per descendent, using default property as Building X data point value.

Siclimat Controller

Create one Building X data point per descendent, using default property as Building X data point value.

Modbus Controller

Create one Building X data point per descendent, using default property as Building X data point value.